ungrounded

How does residual current monitoring work?

RCM - RCD: The difference

RCMs (Residual Current Monitors) monitor residual currents in electrical installations, indicate the present value and signal when the response values are exceeded.

The devices are designed for signalling and/or switching. They comply with DIN EN 62020 (VDE 0663) “Electrical accessories – Residual current monitors for household and similar use (RCMs) (IEC 62020)”.

In contrast to RCMs, RCDs (residual current protective devices) are designed to provide protection in electrical installations in accordance with the standard IEC 60364, e.g. in bathrooms. RCDs always cause a shutdown.

How does an RCM work?

All conductors of the outgoing circuit to be monitored (except the PE conductor) are routed through a measuring current transformer. In a fault-free system, the sum of all currents is equal to zero so that no voltage is induced in the measuring current transformer. If a fault current (IΔ) flows via PE or other paths, the difference in current in the measuring current transformer generates a current flow which is detected by the RCM. This measurement method applies to RCMs for pure AC current and pulsating DC fault currents (type A in accordance with IEC 60755).

AC/DC sensitive RCMAs and RCMBs of type B require special measuring current transformers and a special measurement method to detect both DC and AC currents of different frequencies.

Differences – RCM, RCMA, RCMB, RCMS

RCMs differ in terms of type, frequency and waveform of the currents that they are capable of detecting:

RCM series: Type A residual current monitors in accordance with IEC 60755 for monitoring AC currents (42…2000 Hz) and pulsating DC fault currents.

RCMA, RCMB series: Type B residual current monitors in accordance with IEC 60755 for monitoring AC currents, pulsating and smooth DC fault currents (0…2000 Hz).

RCMS series: Multi-channel type A and B residual current monitoring systems in accordance with IEC 60755 for monitoring AC currents, pulsating and smooth DC fault currents (0 (42)…2000 Hz).

Downloads

NameCategorySizeLanguageTimestampD-/B-Number
Product Overview - Residual Current Monitoring Product Overviews 6.2 MB EN2023/11/0909.11.2023
2020 Guidelines (US) Technical Information 1.9 MB EN2020/06/1515.06.2020
Overview Brochure Product Overviews 10.3 MB EN2023/10/0202.10.2023
Making Gains in Safety - NürnbergMesse Relies on the Monitoring Devices from Bender Technical Article 276.7 KB EN2019/05/1313.05.2019

Products

Ground-Fault Monitoring for Grounded Systems

LINETRAXX® SmartDetect RCMS410

Four-channel DC, AC and pulse current sensitive residual current monitor for earthed AC, AC/DC and DC systems

Ground-Fault Location, Ungrounded

ISOSCAN® EDS440
ISOSCAN® EDS440 Series

Ground-fault location module for ungrounded AC/DC systems

Ground-Fault Monitoring for Grounded Systems

LINETRAXX® SmartDetect RCMS410

Four-channel DC, AC and pulse current sensitive residual current monitor for earthed AC, AC/DC and DC systems

Details

Ground-Fault Location, Ungrounded

ISOSCAN® EDS440
ISOSCAN® EDS440 Series

Ground-fault location module for ungrounded AC/DC systems

Details